Command Configuration Expander

In the Models & Functions tab, the Command Configuration expander lets you set up commands for the property currently selected in the Properties expander. For related procedures, see Setting Up Commands in Object Models.

In particular, you can:

  • Define the command properties of the buttons
  • Define a multiple command for a macro

 

Name

Description

1

Dependency 1

Opens the column for defining the first dependency.

2

Dependency 2

Opens the column for defining the second dependency.

3

Dependency 3

Opens the column for defining the third dependency.

4

New

Opens an entry mask for defining the command rules. Multiple command conditions can be defined.

5

Delete

Deletes the highlighted command condition.

 

Name / Command

Description

1

 

1. Command configuration

2

Command

Command type for selected property (for example, BACnetAnalogWithPriority).

3

Parameter

Displays the parameters dependent on the selected command.

4

Label

Descriptive text for the button. The text is localizable, for example, en-US Manual, de-DE Manuell.

5

Label

Descriptive text for operating value or priority. The text is localizable, for example, en-US Value, de-DE Wert.

6

Name

This text is used for the button that can be executed by scripting. Text is not localizable. The function in the Name column must be unique (for example, WritePrio08, ReleasePrio08).

7

Default Value

Defines the displayed value by the Value text field used:

  • ReferCmdDef (takes the defined value for the selected command function of Command)
  • Provided (takes the value form Value (callout 9) and the value cannot be modified)
  • Runtime (takes the value from the system and must be modified at runtime)
  • DefaultProvided (takes the value from Value (callout 9) and the value can be modified at runtime)

8

Alias

Option to execute multiple commands (for example, alarm acknowledgement) (Alias = Ack).

  • The related command is executed by a macro.
  • A related scope must be defined to ensure only some data points in the project receive the command.

Additional alias texts can be created in the Command Macro text group under Global (HQ) > Base > Texts.

9

Value

Displays the value written during commanding. The value is relevant only if in Default Value (callout 7) the option Provided or DefaultProvided is selected.

10

Group

Defines the Command Groups in the Scope Rights of the security definition (Standard, Event, Advanced, Ownership) used to execute the command.

11

Control

Determines the software control (slider, drop-down list, text field) displayed for operation.

12

Control

Expander: No direct command is executed. Clicking Command opens an entry field for the corresponding values for Value and Priority. The values are sent only with Send.

Default: The command is sent directly to the automation station when In Service or Out of Svc is used.

13

Affected Property

Defines the property used to influence the Command functionality.

14

Filter Property

The defined property will be read at runtime. The assigned enumeration displays the valid text depending on this property.

Example enumeration used:

0 = Close, 1 = Open, 2 = Purge, 3 = Disable, 4 = Enable

Example property read at runtime:

3 = Disable, 4 = Enable

The operating dialog offers the Disable and Enable options only.

15

Combined

If one button is used to execute two or multiple commands, the commands can be linked by selecting the related check box. There are two options: either both commands are executed simultaneously or a command can be selected from a drop-down list box.

Not combined

Combined operation

16

Display

Defines where the function is used:

  • Software (for example, driver scripting, OPC)
  • GenericDisplay (User interface, for example, Status and Command window)
  • GenericDisplayAndSoftware (User interface and drivers)

17

Target Property

Defines which property is affected from this functionality, for example, Present_Value.

18

Logging

Defines when values are written into the History Database (Always, Never or OnFailure).

19

 

2. Command configuration.

20

 

Optional command configuration that integrates third party access into the command execution.

Data Type States

Boolean (Out of Service)

Bit String (Status Flag)

Event (Event State)

True

In alarm

Normal

False

Fault

Fault

n/a

Overridden

Off Normal

 

Out of Service

High limit

 

 

Low limit

 

 

Life safety alarm

Dependency States

Check box key:

  • State is not evaluated
  • State is selected (True)
  • State is cleared (False)

For more information on all available commands, see the Command List, below.

Command List

Expander: No direct command is executed. Clicking Command opens an entry field for the corresponding values for Value and Priority. The values are sent only with the Send command.

Default: The command is sent directly to the automation station when In Service or Out of Svc is used.

Commands

Label

Expander

Control

Provided

Value

Value

Default Control

AutomaticReportExecution

AutomaticRep..

No

ThisDP

 

String

BackupCancel

Cancel

 

Fixed

 

String

BackupExecute

Start

 

Fixed

 

String

BACnetAckAllTransitions

Ack All

No

Fixed

0

String

BACnetAckFault

Ack Fault

No

Fixed

2

String

BACnetAckNormal

Ack Normal

No

Fixed

3

String

BACnetAckOffnormal

Ack Offnormal

No

Fixed

1

String

Backnet AckStatus

Ack All Status

No

Fixed

4

String

BACnetAnalogWithoutPriority

Command

Yes

 

 

 

 

Priority

 

Fixed

8

String

 

Value

 

Prompted

 

String

BACnetAnalogWithPriority

Command

Yes

 

 

 

 

Priority

 

Prompted

8

DropDown

 

Value

 

Prompted

 

Numeric

BACnetBackupDevice

Backup

No

ThisDpe

 

String

BACnetCollectTrend

Collect

No

ThisDpe

 

String

BACnetCommandBitstring

Command Bitstring

Yes

 

 

 

 

Value

 

Prompted

 

Numeric

 

Priority

 

Prompted

0

Numeric

BACnetCommandBitstringWithPriority

Command Bitstring with Priority

Yes

 

 

 

 

Value

 

Prompted

 

String

 

Priority

 

Prompted

8

DropDown

BACnetDeviceColdStart

ColdStart

Yes

 

 

 

 

Type

 

Fixed

0

String

 

Password

 

Prompted

 

Password

BACnetDeviceCommControl

Command

Yes

 

 

 

 

DCC_Value

 

ThisDpe

 

DropDown

 

Password

 

ThisDpe

 

String

 

Duration

 

ThisDpe

 

Numeric

BACnetDeviceWarmStart

WarmStart

Yes

 

 

 

 

Type

 

Fixed

1

String

 

Password

 

Prompted

 

String

BACnetLifeSafety

Command

Yes

 

 

 

 

Operation

 

Prompted

0

DropDown

 

ProcessId

 

Prompted

600

String

 

Source

 

Prompted

 

String

BACnetLifeSafetyNone

None

 

 

 

 

(also used in other LifeSafety objects)

ProcessId

 

Fixed

600

String

(also used in other LifeSafety objects)

Source

 

ThisDpe

 

String

(also used in other LifeSafety objects)

Operation

 

Fixed

2

String

BACnetLifeSafetyReset

Reset

 

Fixed

4

String

BACnetLifeSafetyResetAlarm

Reset-Alarm

 

Fixed

5

String

BACnetLifeSafetyResetFault

Reset-Fault

 

Fixed

6

String

BACnetLifeSafetySilence

Silence

 

Fixed

1

String

BACnetLifeSafetySilenceAudible

Silence-Audible

 

Fixed

2

String

BACnetLifeSafetySilenceVisible

Silence-Visible

 

Fixed

3

String

BACnetLifeSafetyUnsilence

Unsilence

 

Fixed

7

String

BACnetLifeSafetyUnsilenceAudible

Unsilence-Audible

 

Fixed

8

String

BACnetLifeSafetyUnsilenceVisible

Unsilence-Visible

 

Fixed

9

String

BACnetReinitDevice

Reinit

Yes

 

 

 

 

Type

 

ThisDpe

 

DropDown

 

Password

 

Prompted

 

Password

BACnetReleaseWithPriority

Release

Yes

 

 

 

 

Priority

 

Prompted

8

DropDown

BACnetTimeSync

Time-Sync

No.

ThisDpe

 

String

BACnetUnsignedWithoutPriority

Command

Yes

 

 

 

 

Priority

 

Fixed

8

String

 

Value

 

Prompted

 

DropDown

BACnetUnsignedWithPriority

Command

Yes

 

 

 

 

Priority

 

Prompted

8

DropDown

 

Value

 

Prompted

 

DropDown

BACnetWhoIs

Whois

Yes

 

 

 

 

Network

 

Prompted

1

Numeric

 

BeginInstance

 

Prompted

0

Numeric

 

EndInstance

 

Prompted

0

String

BACnetWriteToggleOff

Write

No

Fixed

False

DropDown

BACnetWriteToggleOn

Write

No

Fixed

True

DropDown

GenericWriteBoolean

WriteBool

No

Prompted

 

DropDown

GenericWriteFloat

WriteFloat

No

Prompted

 

Numeric

GenericWriteInt

WriteInt

No

Prompted

 

Numeric

GenericWriteString

WriteString

No

Prompted

 

String

GenericWriteUint

WriteUint

No

Prompted

 

Numeric

JournalCache

JournalCache

No

ThisDpe

 

String

MacroAbort

Abort

No

Fixed

2

Numeric

MacroDisable

Disable

No

Fixed

0

Numeric

MacroEnable

Enable

No

Fixed

1

Numeric

MacroExecute

Execute

No

Fixed

1

Numeric

RequestOwnership

Write

No

Fixed

True

DropDown

TransferOwnership

Write

No

Fixed

True

DropDown

XnetAck

Acknowledge

No

Fixed

0

Numeric

XnetActivate

Activate

No

Fixed

6

Numeric

XnetArm

Include

No

Fixed

4

Numeric

XnetDeactivate

Deactivate

No

Fixed

7

Numeric

XnetDisarm

Disarm

No

Fixed

5

Numeric

XnetReset

Reset

No

Fixed

1

Numeric

XnetSilence

Silence

No

Fixed

2

Numeric

XnetUnsilence

Unsilence

No

Fixed

3

Numeric

 

Most objects also include a target parameter (not listed here).