Start Desigo PX network wizard

Scenario: You want to configure Desigo CC to connect to Desigo PX automation stations. The workflow guides you through the required steps.

 

Reference: For background information, see the Desigo PX section.

 

Flowchart:

 

Prerequisites:

  • The Desigo PX project is created and started in Desigo CC.
  • System Manager is in Engineering mode.
  • System Browser is in Management View.

To speed configuration, make sure the Desigo CC Transaction Mode is set to Simple or the Automatic Switch of Transaction Mode is set to True.
The automatic switch setting is recommended. Without it, to re-enable the logs, you need to set the Transaction Mode to Logging at the end of the configuration procedure.

 

Steps:

1 – Start Network Wizard and Configure Network
  1. Select Project > Field Networks
  1. Click the Network Wizard tab.
  • The Subsystem Desigo Automation Network dialog box opens.
  1. Select the Desigo Automation Network option in the Available Subsystems drop-down list.
  1. Click Next Page .

Configure Network

  • You are in step 2 of 8.
  1. Enter a network name and description.
  1. Click Next Page .

 

2 – Select Driver
  • You are in step 3 of 8.
  1. In the Station Selection drop-down list, select the server.
  1. In the Driver Selection drop-down list box, select one of the following options:
  • New driver
  • Existing driver (skip to step 5)
  1. Click Next Page .

 

3 – Configure Driver Settings
  • You are in step 4 of 8.
  • You selected a new driver.
  1. In the Subsystem Desigo Automation Network expander, enter a name in the Driver description field.
  1. In the Port settings expander, enter the following data:
  • Port ID
  • Network number
  • Network adapter from the drop-down list
  • IP address (is taken over)
  • UDP port
  • Instance number
  1. In the BACnet Advanced Connectivity expander, enter one of the following options in the Type drop-down list:
  • None
  • Foreign device
    a. In the UDP port field, enter the port number.
    b. In the IP address field, enter the address.
  • BBMD
    a. Click Add.
    b. Enter the IP address, UDP port and Subnet mask.
  1. Click Next Page .
    Note: The driver is started automatically prior to data import.

 

4 – Define Views for System Browser
  • You are in step 5 of 8.
  1. Select the Application View check box. Take over the entries from step 2 for Superposed object name and Superposed object display name.
  1. Select the Logical View check box (always selected). Take over the entries from step 2 for Superposed object name and Superposed object display name.
  1. (Optional) Select the User View check box. Take over the entries from step 2 for Superposed object name and Superposed object display name.
  1. Click Next Page .

If you have two or more networks, you can enter the same information as for network 1 in columns Superposed object name and Superposed object display name. This imports the project data to the same folder structure of the System Browser. The entry fields must be completed.

 

5 – Set Import Procedure
  • You are in step 6 of 8.
  1. Select the option:
  • Scan devices if imported online.
  • Automatic import if files are imported from an export file:
    a. Click Browse.
    b. Select the import file.
    c. Click Open.
    d. (Optional) Select check box Import all elements. The files need not be selected manually in step 9a if the check box is selected.
  1. Click Next Page .
    Note: The import is performed in step 9.

 

6 – Not Required in Desigo PX

Step 7 is only displayed if the Desigo building automation and control extension is installed and used.

7 – Summary
  • You are in step 8 of 8.
  1. Click Save.
  1. Click Yes.
  • The network assistant performs all defined steps.

 

8a – Start Data Import with Select Files
  • You selected Automatic Import in step 6.
  • You cleared check box Import all elements in step 6.
  1. Click the Source list .
    Note: If Delete unselected items from the views is selected, all automation stations and the associated objects that are not in the selected import file are deleted. The main nodes must be manually deleted in Views for Logical View and User View.
  1. Click Import.
  • The import procedure starts with the first file in the Items to Import list. The state can be: Completed, Failed, In progress (%), Partially completed, [number of failed instances].
  • A message is displayed at the end of the import process that summarizes the results in a detailed log. Click Import log.
  • Note: The import is not executed if the number of data points exceeds system limits. Check the Number of data points entered in project size.
  1. Click OK.

 

8b – Start Data Import with Scan Devices

You selected Scan device in step 6.

 

(Optional) Search Device ID with the BACnet Object Browser

  1. Open the Windows Start menu and select All Programs > [Vendor Name] > Desigo CC > Tools > BACnet Object Browser.
  • The BACnet Object Browser scans the network for BACnet devices.
    Note: If multiple networks have been defined, they are not displayed using the defined network names. The designation in the BACnet Object Browser is System1_1, System1_2, System1_3, and so on.
  1. Select a device from the system tree in the left pane.
  • The right pane is updated with all associated information on the device, sorted by property name and value column.
  1. For subsequent AutoDiscovery in tab Network devices (application of a filter), note the following data:
  • vendor-identifier
  • object-identifier
  • The device data for the online import into Desigo CC are established.

No communication is available

Possible cause

Perform the following steps ...

Management station is on the same network:

  • No foreign device defined
  • IP Address does not reference the BBMD device on the network.
  • UDP port not correctly defined.
  1. Select Management View > Project > Management System > Server > Drivers > [driver name].
  2. Select the BACnet tab and open the BT BACnet Stack Config expander.
  3. Check the settings for Port Properties > Foreign-Device.
    The IP address must reference the BBMD device of the network.

BACnet driver not working.

  1. Select Management > Project > Management System > Server > Drivers > [driver name].
  2. Click the Extended Operation tab.
  3. Select Manager Status and click Start.

The firewall does not allow the BACnet driver.

  1. Add GMS BACnet Driver under Allow communication of Apps through Windows Defender Firewall.

Starting a Network Scan

  • You have completed the optional Scan by Device ID workflow and the information needed to filter is available.
  1. Select the Network device tab.
  1. Open the Discovery Settings expander.
  1. In the field Scan timeout in seconds, enter the maximum duration of a scan (Default: 60 seconds).
  1. Select Enable device discovery. The Desigo CC project data base is automatically updated if the Desigo CC project data base deviates from the data base ID on the automation station.
  1. Select the filter criterion:
  • Use network filter and enter the Network number filter.
  • Use instance filter and enter the Beginning instance and Ending instance (object-identifier).
  • Use vendor filter and enter a Vendor ID.
  • Use a Specific instance filter and enter the instance number.
  1. Click Save .
  1. Select the Device recognition expander and click Scan. The device scan operates for the period entered in Scan timeout in seconds after the set period if the Cancel button is selected. Cancel prematurely cancels the scan.
  • Discovered devices are displayed in the Device recognition expander in the Network scan pane.
  1. Select check box Import selection for each automation station for import.
  1. Click Import.
  1. Click Yes.
  • The progress displays in the Scan status section. This may take a few minutes depending on the amount of data.
  • Data points are displayed in System Browser below the selected network.