Creating a Reaction to Unblock and Unlock Doors in Case of Life-Safety Events
Scenario: You want the system to automatically unblock doors is a fire alarm occurs. For background information, see Reactions.
- System Manager is in Engineering mode.
- In System Browser, select Application View.
- Select Applications > Logics > Reactions.
- The Reaction Editor tab displays.
- (Optional) Click to create a new folder, then enter a Name and Description, for example
Life safety reactions
.
- From the Triggers expander, open Event.
- Depending on the UL or ULC event schema you use do one of the following:
- For UL, click New to display a new instruction (row), then,
in Category, select = Life Safety
- For ULC, click New four times to display four new instructions (rows), then set Category as follows:
- Fire Alarm
- MNS1
- MNS2
- Emergency
- From the Output expander, open Action.
- In System Browser, select the Manual navigation check box.
- Expand Field Networks > [SiPass Network].
- From the access control network structure, drag the first door to open to ensure a safe way out.
- The Action expander displays a new instruction (row).
- In Property, select Block Status.
- In Command, select Unblock.
- Drag the same door again from System Browser to create a new instruction.
- In Property, select Lock Status.
- In Command, select Unlock.
- Repeat steps 9 to 14 as many times as necessary to open all required doors.
- Click Save As .
- In the Save Object As dialog box, select the main Reactions folder or any subfolder under it as the destination where you want to save this reaction:
a. Enter a Name and Description, for exampleOpen doors for fire safety escape
.
b. Click OK.
- The new reaction is added to System Browser, and is enabled by default.
- In System Browser, clear the Manual navigation check box.