Migrating and Upgrading FC720 Cerberus Pro Fire Panels
Upgrading Control Panels from V5.2 to V6.0
- If no changes occurred in the fire system, then no re-import of the SiB-X metafile is required in Desigo CC.
Upgrading Control Panels from V6.0 to V7.0
- Re-import of the V7.0 SiB-X metafile is required in Desigo CC.
Upgrade Desigo CC from Previous Versions
When you upgrade Desigo CC from V3.x/V4.x to V5.0, just follow the standard Desigo CC upgrade procedure.
Then, in the Desigo CC project, re-import the SiB-X metafile on each fire system to apply the latest library modifications.
Expanding Control Panels
It is possible to expand the fire panels as follows:
- FC722 to FC724
- FC722 to FC726
- FC724 to FC726
A new import of the SiB-X metafiles is required. Existing object references in graphics, macros, user defined views, schedules and so on are still valid after the new SiB-X import.
Replacing NK823x as router for the SafeDlink communication
NK823x used to be applied as network router for the FS720 SafeDLink in DMS8000 installations. In connection to Desigo CC, NK823x no longer supports FS720.
In case of migration, you can replace NK823x with Scalance S615. For more information, see the Scalance S615 documentation.