Control using a Central Function

The central function overrides local room operation. The required operating mode in the room can be commanded again after successful central override.

Prerequisites:

  • The system browser is in Operating mode.
  • In System Browser, Management View is selected.
  • The online connection is established.

 

Switching on Lighting
  1. Select Applications > Logics > Central Functions > [Hierarchy Name] > Light [Category] > [Central Lighting (CenOpLgt)].
  • The associated lighting objects are displayed in the Central Function Viewer.
  1. Click the Operation tab.
  1. Do the following:
  • For priority 13, select the Command user (13) property and click Manual.
  • For priority 8, select the Command manual (8) property and click Manual.
  1. In the Value drop-down list, select the illuminance.
  1. Click Send.
  • The message Command successful appears.

 

Controlling Blinds
  1. Select Applications > Logics > Central Functions > [Hierarchy Name] > Blinds [Category] > [Central Blinds Control (CenOpShd)].
  • The associated blinds objects are displayed in the Central Function Viewer.
  1. Click the Operation tab.
  1. Do the following:
  • For priority 13, select the Command user (13) property and click Manual.
  • For priority 8, select the Command manual (8) property and click Manual.
  1. In the Value drop-down list, select the blinds position.
  1. Click Send.
  • The message Manual successful is displayed.

 

Changing Room Operating Mode
  1. Select Applications > Logics > Central Functions > [Network name], property User command (13) [Category] > [Central Operating Mode (CenOpMod)].
  • The associated operating modes are displayed in the Central Function Viewer.
  1. In the Operation tab, select the User command (13) property.
    a. Click Manual.
    b. In the Value drop-down list, select the operating mode.
    c. Click Send.
  • The message Command successful appears.